Type USVG
Single-phase direct current supply
non stabilized

Transformer to VDE 0551 / EN 60742
Protective class I
Protective type IP 00
Thermal class B
Nominal ambient temperature ta 60°C
Input voltage : AC 230V
± 5% or
---------------------AC 400V ± 5%
Frequency: 50/60Hz
Output voltage : nach DIN 19240 DC 24V
Ripple factor: < 5% by rated current
Excess voltage protection by varistor
Output overload protection
Unit fuse
Mounting brackets DIN 41307
Terminal connection VBG 4




typ power Output
current
efficiency
measure (mm) weight
W A DC % A B C D E F kg
USVG 230/24-1
USVG 230/24-3
USVG 230/24-5
USVG 230/24-10

USVG 400/24-1
USVG 400/24-3
USVG 400/24-5
USVG 400/24-10
24
72
120
240

24
72
120
240
1
3
5
10

1
3
5
10
69
77
80
80

69
77
80
80
78
84
105
105

78
84
105
105
124
149
155
185

124
149
155
185
105
117
124
124

105
117
124
124
56
64
84
84

56
64
84
84
99
125
133
162

99
125
133
162
4,8
4,8
5,8
5,8

4,8
4,8
5,8
5,8
1,42
2,31
3,25
4,70

1,42
2,31
3,25
4,70



Lastabhänigkeit der Ausgangspannung
gemäß DIN 19240